modelTwoBusesPowerTransferTransmissionLine

Diagram of TwoBusesPowerTransferTransmissionLine

Extends from Modelica.Icons.Example (Icon for runnable examples).

Information

This model demonstrates the transmission of active power through a purely inductive transmission line, connected to two infinite buses with a phase-to-phase voltage of 10 kV. The generator at portA of the line has 30 deg phase, the other one has 0 deg phase. The reactance of each conductor is 1 Ohm.

The active power flow from portA to portB is

P = 3(VA*VB)/X*sin(delta)= UA*UB/X*sin(delta) = 50 MW.

By choosing a base power of 100 MW and a base voltage of 10 kV, the active power flow from portA to portB is 0.5 p.u.

Components

TypeNameDefaultDescription
PowerGrids.Electrical.Buses.InfiniteBusinfiniteBusA
PowerGrids.Electrical.SystemsystemPowerGrids
PowerGrids.Electrical.Branches.LineConstantImpedancetransmissionLine
PowerGrids.Electrical.Buses.InfiniteBusinfiniteBusB