modelDynamicReliefValve

Dynamic relief valve
Diagram of DynamicReliefValve

Information

## Copyright © EDF 2002 - 2026   
## ThermoSysPro Version 4.2   
This component model is documented in Sect. 13.13 of the ThermoSysPro book.

Parameters

TypeNameDefaultDescription
Units.SI.AbsolutePressurePopen3e5Pressure that opens the valve
Units.SI.AbsolutePressurePout1e5Pressure at the valve outlet (for sizing)
ThermoSysPro.Units.xSI.CvCvmax8005.42Maximum Cv [USG/min]
Real[:,2]caract[0, 0; 1, Cvmax]Position vs. Cv [USG/min] characteristics (active if mode_caract=1)
Units.SI.AreaA10.1Hydraulic area upstream the clapper
Units.SI.AreaA20.125Hydraulic area downstream the clapper
Units.SI.Area[:,2]clapper_area[0, A1; 0.01, A2; 1, A2]Clapper area as a function of the clapper elevation
RealD1Damping
Units.SI.Massm1Valve mass
Units.SI.Lengthz_max0.1Maximum clapper elevation
RealKe62500Valve spring stiffness
RealCd0Drag coefficient of the clapper
Integermode_caract00:linear characteristics - 1:characteristics is given by caract[] - 2:characteristics for conic clapper
Integeroption_interpolation11: linear interpolation - 2: spline interpolation (active if mode_caract=1)
Booleanmech_steady_statetruetrue: start from mechanical steady state - false: start from 0
Units.SI.Lengthz00Initial clapper elevation, between 0 and z_max. 0:valve closed - z_max: valve fully open (active if mech_steady_state=false)
Units.SI.MassFlowRategamma_diff1e-4Diffusion conductance (active if diffusion=true in neighbouring volumes)
Fluid › Fluid properties
Units.SI.Densityp_rho0If > 0, fixed fluid density
IF97RegionregionIF97Region.All_regionsIF97 region (active for IF97 water/steam only)

Connectors

TypeNameDefaultDescription
ThermoSysPro.Fluid.Interfaces.Connectors.FluidInletC1
ThermoSysPro.Fluid.Interfaces.Connectors.FluidOutletC2

Components

TypeNameDefaultDescription
Booleanclapper_is_freetrue if clapper is free to move in both directions, false otherwise
Units.SI.ForceFpGravity force
Units.SI.ForceFrSpring force
Units.SI.ForceFdDamping force
Units.SI.ForceFhHydraulic force
Units.SI.ForceFdynDynamic pressure force
Units.SI.ForceFtTotal force
Units.SI.LengthzClapper elevation
Units.SI.Velocityvder(z)Clapper velocity
Units.SI.Accelerationader(v)Clapper acceleration
RealOuvValve position
Units.SI.AreaAHydraulic area upstream the clapper
Units.SI.ForceFr_minSpring force when valve is closed
ThermoSysPro.Units.xSI.CvCvCv [USG/min]
Units.SI.MassFlowRateQMass flow rate
ThermoSysPro.Units.SI.PressureDifferencedeltaPSingular pressure loss
Units.SI.DensityrhoFluid density
Units.SI.TemperatureTFluid temperature
Units.SI.AbsolutePressurePmFluid average pressure
Units.SI.SpecificEnthalpyhFluid specific enthalpy
Units.SI.AbsolutePressurePdynDynamic pressure on the clapper
Units.SI.VelocityvhFluid velocity through the valve
Units.SI.EnergyWdynDissipated fluid kinetic energy
RealRerho*(vh - v)*sqrt(4*A/pi)/ThermoSysPro.Properties.WaterSteam.IF97.DynamicViscosity_rhoT(rho, T)Clapper Reynolds

Revisions

Author  

Daniel Bouskela