modelStaticWaterWaterExchanger

Static plate heat exchanger
Diagram of StaticWaterWaterExchanger

Information

## Copyright © EDF 2002 - 2026  
## ThermoSysPro Version 4.2  
This component model is documented in Sect. 9.6.2 of the ThermoSysPro book.   
# Static water water exchanger   
   
This static plate heat exchanger is the steady-state version of the [dynamic water water exchanger](modelica://ThermoSysPro.WaterSteam.HeatExchangers.DynamicWaterWaterExchanger).  
In addition to the [dynamic model](modelica://ThermoSysPro.WaterSteam.HeatExchangers.DynamicWaterWaterExchanger) assumptions, the specific heats and mass flow rates of both fluids are supposed constant.  


## Modelica component model  

The equations mentioned below are implemented in the component *StaticWaterWaterExchanger*, located in the *WaterSteam.HeatExchangers* sub-library.   
   
![modelica://ThermoSysPro/UsersGuide/Documentation/ThermoSysPro.WaterSteam.HeatExchangers.StaticWaterWaterExchanger.svg](modelica://ThermoSysPro/UsersGuide/Documentation/ThermoSysPro.WaterSteam.HeatExchangers.StaticWaterWaterExchanger.svg)  

## Nomenclature  

| Symbol| Description| Unit| Definition| Modelica name |  
| :----------------------------------- | :------------------------------------------------------------------------------------------- | :------------------------------------------- | :---------------------------------------------------------------------- | :----------- |  
| \\(A\\)| Heat exchange surface| \\(\mathrm{m}^{2}\\)| \\(\left\(N\_{\mathrm{p}}-2\right\) \cdot S\_{\mathrm{p}}\\)| S |  
| \\(m\_{\mathrm{h}}\\)| Hot fluid mass flow rate| \\(\mathrm{kg} / \mathrm{s}\\)|| Qc |  
| \\(m\_{\mathrm{c}}\\)| Cold fluid mass flow rate| \\(\mathrm{kg} / \mathrm{s}\\)|| Qf |  
| \\(N\_{\mathrm{c}}\\)| Number of channels of each fluid| \\(-\\)| \\(\left\(N\_{\mathrm{p}}-1\right\) / 2\\)| N |  
| \\(N\_{\mathrm{p}}\\)| Number of plates| \\(-\\)|| nbp |  
| \\(P\_{\mathrm{c}, \mathrm{i}}\\) | Cold fluid pressure at the inlet| \\(\mathrm{Pa}\\)|| Ef.P |  
| \\(P\_{\mathrm{c}, \mathrm{o}}\\) | Cold fluid pressure at the outlet| \\(\mathrm{Pa}\\)|| Sf.P |  
| \\(P\_{\mathrm{h}, \mathrm{i}}\\) | Hot fluid pressure at the inlet| \\(\mathrm{Pa}\\)|| Ec.P |  
| \\(P\_{\mathrm{h}, \mathrm{o}}\\) | Hot fluid pressure at the outlet| \\(\mathrm{Pa}\\)|| Sc.P |  
| \\(T\_{\mathrm{c}, \mathrm{i}}\\) | Cold fluid temperature at the inlet| \\(\mathrm{K}\\)|| Tef |  
| \\(T\_{\mathrm{c}, \mathrm{o}}\\) | Cold fluid temperature at the outlet| \\(\mathrm{K}\\)|| Tsf |  
| \\(T\_{\mathrm{h}, \mathrm{i}}\\) | Hot fluid temperature at the inlet| \\(\mathrm{K}\\)|| Tec |  
| \\(T\_{\mathrm{h}, \mathrm{o}}\\) | Hot fluid temperature at the outlet| \\(\mathrm{K}\\)|| Tsc |  
| \\(U\\)| Global heat transfer coefficient \(internal overall heat exchange coefficient\)| \\(\mathrm{W} / \mathrm{m}^{2} / \mathrm{K}\\) || K |  
| \\(W\\)| Thermal power exchanged between the two fluids| \\(\mathrm{W}\\)|| W |  
| \\(\Delta T\_{1}\\)| Temperature difference 1| \\(\mathrm{K}\\)| For counter flow \\(T\_{\mathrm{h}, \mathrm{i}}-T\_{\mathrm{c}, \mathrm{o}}\\) For parallel flow \\(T\_{\mathrm{h}, \mathrm{i}}-T\_{\mathrm{c}, \mathrm{i}}\\) | DT1 |  
| \\(\Delta T\_{2}\\)| Temperature difference 2| \\(\mathrm{K}\\)| For counter flow \\(T\_{\mathrm{h}, \mathrm{o}}-T\_{\mathrm{c}, \mathrm{i}}\\) For parallel flow \\(T\_{\mathrm{h}, \mathrm{o}}-T\_{\mathrm{c}, \mathrm{o}}\\) | DT2 |  
| \\(\Lambda\_{\mathrm{c}}\\)| Friction pressure loss coefficient of the entire length of the exchanger for the cold fluid | \\(\mathrm{m}^{-4}\\)|| p_Kf |  
| \\(\Lambda\_{\mathrm{h}}\\)| Friction pressure loss coefficient of the entire length of the exchanger for the hot fluid| \\(\mathrm{m}^{-4}\\)|| p_Kc |  
| \\(\rho\_{\mathrm{c}}\\)| Cold fluid density| \\(\mathrm{kg} / \mathrm{m}^{3}\\)|| rhof |  
| \\(\rho\_{\mathrm{h}}\\)| Hot fluid density| \\(\mathrm{kg} / \mathrm{m}^{3}\\)|| rhoc |  



## Governing equations  

### Energy balance equation \(hot fluid\)  


    
    

- Validity domain:   
   
 \\(\forall \dot{m}\_{\mathrm{h}}\\)  

- Mathematical formulation:   
   
 $$W=\dot{m}\_{\mathrm{h}} \cdot c\_{p, \mathrm{h}} \cdot\left\(T\_{\mathrm{h}, \mathrm{i}}-T\_{\mathrm{h}, \mathrm{o}}\right\)$$  


### Energy balance equation \(cold fluid\)  


    
    

- Validity domain:   
   
 \\(\forall \dot{m}\_{\mathrm{c}}\\)  

- Mathematical formulation:   
   
 $$W=\dot{m}\_{\mathrm{c}} \cdot c\_{p, \mathrm{c}} \cdot\left\(T\_{\mathrm{c}, \mathrm{o}}-T\_{\mathrm{c}, \mathrm{i}}\right\)$$  


### Heat exchanged between the fluid and the wall  


    
    

- Validity domain:   
   
 \\(\dot{m}\_{\mathrm{h}} \neq 0, \dot{m}\_{\mathrm{c}} \neq 0, \Delta T\_{1} \neq 0\\) and \\(\Delta T\_{2} \neq 0\\)  

- Mathematical formulation:   
   
 $$W=U \cdot A \cdot \frac{\Delta T\_{2}-\Delta T\_{1}}{\ln \left\(\frac{\Delta T\_{2}}{\Delta T\_{1}}\right\)}$$  

- Comments:   
   



### Momentum balance equation \(hot fluid\)  


    
    

- Validity domain:   
   
 \\(\forall \dot{m}\_{\mathrm{h}}\\)  

- Mathematical formulation:   
   
 $$P\_{\mathrm{h}, \mathrm{o}}=P\_{\mathrm{h}, \mathrm{i}}-\Lambda\_{\mathrm{h}} \cdot \frac{\dot{m}\_{\mathrm{h}} \cdot \lvert \dot{m}\_{\mathrm{h}}\rvert}{N\_{\mathrm{c}}^{2} \cdot \rho\_{\mathrm{h}}}$$  

- Comments:   
   



### Momentum balance equation \(cold fluid\)  


    
    

- Validity domain:   
   
 \\(\forall \dot{m}\_{\mathrm{c}}\\)  

- Mathematical formulation:   
   
 $$P\_{\mathrm{c}, \mathrm{o}}=P\_{\mathrm{c}, \mathrm{i}}-\Lambda\_{\mathrm{c}} \cdot \frac{\dot{m}\_{\mathrm{c}} \cdot \lvert \dot{m}\_{\mathrm{c}}\rvert }{N\_{\mathrm{c}}^{2} \cdot \rho\_{\mathrm{c}}}$$  

- Comments:   
   


## References   
   
El Hefni, Baligh and Bouskela, Daniel (2019). [Modeling and Simulation of Thermal Power Plants with ThermoSysPro](https://link.springer.com/book/10.1007/978-3-030-05105-1), sect. 9.6.2. Springer Nature Switzerland AG.

Parameters

TypeNameDefaultDescription
Units.SI.ThermalConductivitylambdam15.0Metal thermal conductivity
Units.SI.CoefficientOfHeatTransferp_hc6000Heat transfer coefficient for the hot side if not computed by the correlations
Units.SI.CoefficientOfHeatTransferp_hf3000Heat transfer coefficient for the cold side if not computed by the correlations
Realp_Kc100Pressure loss coefficient for the hot side if not computed by the correlations
Realp_Kf100Pressure loss coefficient for the cold side if not computed by the correlations
Units.SI.Thicknessemetal0.0006Wall thickness
Units.SI.AreaSp2Plate area
Realnbp499Number of plates
Realc11.12647Correction coefficient
Units.SI.Densityp_rhoc0If > 0, fixed fluid density for the hot fluid
Units.SI.Densityp_rhof0If > 0, fixed fluid density for the cold fluid
Integermodec0IF97 region for the hot fluid. 1:liquid - 2:steam - 4:saturation line - 0:automatic
Integermodef0IF97 region for the cold fluid. 1:liquid - 2:steam - 4:saturation line - 0:automatic
Integerexchanger_type1Exchanger type - 1: countercurrent. 2: cocurrent
Integerheat_exchange_correlation1Correlation for the computation of the heat exchange coefficient - 0: no correlation. 1: SRI correlations
Integerpressure_loss_correlation1Correlation for the computation of the pressure loss coefficient - 0: no correlation. 1: SRI correlations

Connectors

TypeNameDefaultDescription
Connectors.FluidInletEc
Connectors.FluidInletEf
Connectors.FluidOutletSf
Connectors.FluidOutletSc

Components

TypeNameDefaultDescription
Units.SI.PowerWThermal power exchanged between the two sides
ThermoSysPro.Units.SI.PressureDifferenceDPcPressure loss of the hot fluid
ThermoSysPro.Units.SI.PressureDifferenceDPfPressure loss of the cold fluid
Units.SI.CoefficientOfHeatTransferhcHeat transfer coefficient of the hot fluid
Units.SI.CoefficientOfHeatTransferhfHeat transfer coefficient of the cold fluid
Units.SI.CoefficientOfHeatTransferKGlobal heat transfer coefficient
Units.SI.AreaSHeat exchange surface
Units.SI.TemperatureTecFluid temperature at the hot inlet
Units.SI.TemperatureTscFluid temperature at the hot outlet
Units.SI.TemperatureTefFluid temperature at the cold inlet
Units.SI.TemperatureTsfFluid temperature at the cold outlet
ThermoSysPro.Units.SI.TemperatureDifferenceDTmDifference in average temperature
ThermoSysPro.Units.SI.TemperatureDifferenceDT1Temperature difference at the inlet of the exchanger
ThermoSysPro.Units.SI.TemperatureDifferenceDT2Temperature difference at the outlet of the exchanger
RealDT12DT1/DT2 (s.u.)
Units.SI.MassFlowRateQcMass flow rate of the hot fluid
Units.SI.MassFlowRateQfMass flow rate of the cold fluid
Realqmc
Realqmf
Realquc
Realquf
RealN
Units.SI.DensityrhocHot fluid density
Units.SI.DensityrhofCold fluid density
Units.SI.DynamicViscositymucHot fluid dynamic viscosity
Units.SI.DynamicViscositymufCold fluid dynamic viscosity
Units.SI.ThermalConductivitylambdacHot fluid thermal conductivity
Units.SI.ThermalConductivitylambdafCold fluid thermal conductivity
Units.SI.TemperatureTmcHot fluid average temperature
Units.SI.TemperatureTmfCold fluid average temperature
Units.SI.AbsolutePressurePmcHot fluid average pressure
Units.SI.AbsolutePressurePmfCold fluid average pressure
Units.SI.SpecificEnthalpyHmcHot fluid average specific enthalpy
Units.SI.SpecificEnthalpyHmfCold fluid average specific enthalpy
ThermoSysPro.Properties.WaterSteam.Common.ThermoProperties_phproce
ThermoSysPro.Properties.WaterSteam.Common.ThermoProperties_phprocs
ThermoSysPro.Properties.WaterSteam.Common.ThermoProperties_phprofe
ThermoSysPro.Properties.WaterSteam.Common.ThermoProperties_phprofs
ThermoSysPro.Properties.WaterSteam.Common.ThermoProperties_phproc
ThermoSysPro.Properties.WaterSteam.Common.ThermoProperties_phprof

Revisions

Author  

Daniel Bouskela