modelCoolingCoilHumidifyingHeating_OpenLoop

Model of a air handling unit that tests variable mass flow rates

Extends from Modelica.Icons.Example, Buildings.Applications.DataCenters.ChillerCooled.Equipment.Validation.BaseClasses.PartialAirHandlerMassFlow.

Information

This model demonstrates the use of Buildings.Applications.DataCenters.ChillerCooled.Equipment.CoolingCoilHumidifyingHeating for different inlet conditions.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.ThermalConductanceUA_nominalm2_flow_nominal*1006*(12 - 26)/Buildings.Fluid.HeatExchangers.BaseClasses.lmtd(T_a1_nominal, T_b1_nominal, T_a2_nominal, T_b2_nominal)Thermal conductance at nominal flow for sensible heat, used to compute time constant
RealyValMin0.4Minimum position of water-side valves

Components

TypeNameDefaultDescription
Buildings.Applications.DataCenters.ChillerCooled.Equipment.CoolingCoilHumidifyingHeatingahuAir handling unit
Buildings.Fluid.Sensors.RelativeHumidityTwoPortsenRelHumSensor for relative humidity
Modelica.Blocks.Sources.ConstantuValControl signal for water valve
Modelica.Blocks.Sources.ConstanttemSetTemperature setpoint
Modelica.Blocks.Sources.ConstantXSetMass fraction set point
Modelica.Blocks.Sources.ConstantuFanControl input for fan

Revisions

  • May 13, 2021, by Michael Wetter:
    Set start value of valve to avoid unreasonably large pressure drop due to prescribed mass flow rate that was forced through a closed valve.
    This is for #2488.
  • April 11, 2017, by Yangyang Fu:
    First implementation.