modelLargeScaleWaterToWater
Large scale water to water chiller
Extends from Modular, Buildings.Fluid.HeatPumps.ModularReversible.BaseClasses.LargeScaleWaterToWaterDeclarations.
Information
Large scale water-to-water chiller, using the Buildings.Fluid.Chillers.ModularReversible.Modular approach.
Contrary to the standard sizing approach for the Buildings.Fluid.Chillers.ModularReversible.Modular models, the parameters are based on an automatic estimation as described in Buildings.Fluid.HeatPumps.ModularReversible.BaseClasses.LargeScaleWaterToWaterDeclarations.
For more information on the approach, see UsersGuide.
The documentation of the model for cooling is at Buildings.Fluid.Chillers.ModularReversible.RefrigerantCycle.TableData2D.
Assumptions
- As heat losses are implicitly included in measured data in manufacturer dataseheets, heat losses are disabled.
- Pressure losses are not provided in datasheets. As typical values are unknown, the pressure loss is set to 0 to enable easier usage. However, the parameter is not final and should be replaced if pump electrical power consumption is of interest for your simulation aim.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Real | scaFac | refCyc.refCycChiCoo.scaFac | Scaling factor of chiller |
| Buildings.Fluid.Chillers.ModularReversible.Data.TableData2D.Generic | datTab |
Revisions
-
Novemeber 11, 2022 by Fabian Wuellhorst:
Implemented #1576)