modelTableData2D

Reversible heat pump based on 2D manufacturer data

Extends from Buildings.Fluid.HeatPumps.ModularReversible.Modular.

Information

Heat pump based on two-dimensional data from manufacturer data, (e.g. based on EN 14511), using the Buildings.Fluid.HeatPumps.ModularReversible.Modular approach.

For more information on the approach, see Buildings.Fluid.HeatPumps.ModularReversible.UsersGuide.

Internal inertias and heat losses are typically neglected, as these are implicitly obtained in measured data from manufacturers. Also, icing is disabled as the performance degradation is already contained in the data.

Sizing

At the nominal conditions, the refrigerant cycle model will calculate the unscaled nominal heat flow rate, which is named QHeaNoSca_flow_nominal for heat pumps and QCooNoSca_flow_nominal for chillers. This value is probably different from QHea_flow_nominal and QCoo_flow_nominal which is for sizing. For example, suppose you need a 7.6 kW heat pump, but the datasheets only provides 5 kW and 10 kW options. In such cases, the performance data and relevant parameters are scaled using a scaling factor scaFac. Resulting, the refrigerant machine can supply more or less heat with the COP staying constant. However, one has to make sure that the movers in use also scale with this factor. Note that most parameters are scaled linearly. Only the pressure differences are scaled quadratically due to the linear scaling of the mass flow rates and the basic assumption:

k = ṁ ⁄ √ Δp  

Both QHeaNoSca_flow_nominal or QCooNoSca_flow_nominal and scaFac are calculated in the refrigerant cycle models.

Please read the documentation of the model for heating at Buildings.Fluid.HeatPumps.ModularReversible.RefrigerantCycle.TableData2D.

For cooling, the assumptions are similar, and described at Buildings.Fluid.Chillers.ModularReversible.RefrigerantCycle.TableData2D

References

EN 14511-2018: Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors https://www.beuth.de/de/norm/din-en-14511-1/298537524

Parameters

TypeNameDefaultDescription
RealscaFacHearefCyc.refCycHeaPumHea.scaFacScaling factor of heat pump
RealscaFacCoorefCyc.refCycHeaPumCoo.scaFacScaling factor for cooling mode
Buildings.Fluid.HeatPumps.ModularReversible.Data.TableData2D.GenericHeatPumpdatTabHea
Buildings.Fluid.Chillers.ModularReversible.Data.TableData2D.GenericdatTabCoo
Advanced
Modelica.Blocks.Types.SmoothnesssmoothnessModelica.Blocks.Types.Smoothness.LinearSegmentsSmoothness of table interpolation
Modelica.Blocks.Types.ExtrapolationextrapolationModelica.Blocks.Types.Extrapolation.LastTwoPointsExtrapolation of data outside the definition range