modelBasicControlValve

Basic valve model with optional flow characteristics for incompressible fluids

Extends from ThermofluidStream.FlowControl.Internal.PartialValve.

Information

This model serves for most incompressible applications where basic control valves are needed.


The modeler has the ability to choose between different valve characteristics and flow coefficients.

The three standard curve characteristics (linear, parabolic, equal-percentage) are implemented and can be chosen.


To conclude the parameterization, a flow coefficient has to be set. Most data sheets of valves deliver a corresponding "KVs (CVs)"-Value. Otherwise a nominal mass-flow rate can be set.

For incompressible flow, the reference values for density (1g/cm3) and pressure (1bar) should be unchanged.

Reference values for standardized flow coefficients

When using Kvs, Cvs_US, or Cvs_UK, the default values dp_ref = 1 bar and rho_ref = 1000 kg/m3 must not be modified.

Changing these reference values currently leads to incorrect model behavior. The assertion level can be configured using assertionLevel. To test this behavior, a test model has been setup in ValveReferenceValues.

Parameters

TypeNameDefaultDescription
Valve parameters
FlowCoeffTypeflowCoefficientFlowCoeffType.KvsSelect type of flow coefficient
RealKvs0Kvs-value (metric) from data sheet (valve fully open)
RealCvs_US0Cvs-value (US [gal/min]) from data sheet (valve fully open)
RealCvs_UK0Cvs-value (UK [gal/min]) from data sheet (valve fully open, deprecated; use Kvs or Cvs_US instead)
SI.MassFlowRatem_flow_ref_set0Reference mass flow rate
Advanced
AssertionLevelassertionLevelAssertionLevel.errorAssertion level for invalid reference values

Contents

NameDescription
valveCharacteristics