modelHeatPumpSystem

Heat pump system with storage and controller, input: heat demand, output: electrical power
Diagram of HeatPumpSystem

Information

1. Purpose of model

Combination of storage tank, heat pump, supplementary electric heater and controller.

2. Level of detail, physical effects considered, and physical insight

(Purely technical component without physical modeling.)

3. Limits of validity

(Purely technical component without physical modeling.)

4. Interfaces

HeatFlowRateIn Q_Demand

Powerport epp


5. Nomenclature

(no elements)

6. Governing Equations

(no equations)

7. Remarks for Usage

(no remarks)

8. Validation

(no validation or testing necessary)

9. References

(no remarks)

10. Version History

Model from TransiEnt 1.1.0 modified by Anne Hagemeier (anne.hagemeier@umsicht.fraunhofer.de), Nov 2019

Parameters

TypeNameDefaultDescription
Control
BooleanModulatingtrueTrue: modulating heat pump operation, false: static operation with P_n
BooleanMinTimestrueIf true, minimum operation and shutoff times are considered
BooleanCalculatePHeaterfalseIf true, electrical heater power output is calculated for bivalent heat pump operation
Booleancontrol_SoCfalseChoose controlled variable, 'true'=SoC, 'false'=Storage temperature
TransiEnt.Basics.Types.OnOffRelaisStatusinit_stateTransiEnt.Basics.Types.on_readyState of relais at initialization
SI.TemperatureDifferenceDelta_T_db2Deadband of hysteresis control
Heat storage
SI.TemperatureT_s_min303.15Minimum storage temperature
SI.VolumeV_Storage0.5Volume of the Storage
SI.Heightheight1.3Height of heat storage
Modelica.Units.NonSI.Temperature_degCT_amb15Assumed constant temperature in tank installation room
SI.SurfaceCoefficientOfHeatTransferk0.08Coefficient of heat transfer through tank surface
Storage parameters
SI.Diameterdsqrt(4*V_Storage/Modelica.Constants.pi/height)Diameter of heat storage
Heatpump
BooleanusePowerPorttrueTrue if power port shall be used
Booleanuse_T_source_input_KfalseFalse, use outer ambient conditions
SI.TemperatureDifferenceDelta_T_internal5Temperature difference between refrigerant and source/sink temperature
SI.HeatFlowRateQ_flow_n3.5e3Nominal heat flow of heat pump at nominal conditions according to EN14511
RealCOP_n3.7Coefficient of performance at nominal conditions according to EN14511
Heater
SI.PowerP_el_n10e3Nominal electric power of the backup heater
SI.Efficiencyeta_Heater0.95Efficiency of the backup heater

Connectors

TypeNameDefaultDescription
PowerPortModelepp
TransiEnt.Basics.Interfaces.Thermal.HeatFlowRateInQ_Demand

Components

TypeNameDefaultDescription
TransiEnt.SimCentersimCenter
SI.TemperatureT_set323.15Output temperature of the heat pump
SI.TemperatureT_sourcesimCenter.ambientConditions.temperature.value + 273.15Temperature of heat source
Storage.Heat.HotWaterStorage_constProp_L2.HotWaterStorage_constProp_L2heatStorage
Modelica.Blocks.Sources.RealExpressionrealExpression
TransiEnt.Producer.Heat.Power2Heat.Heatpump.BivalentHeatPumpWithControlheatPumpWithControl

Contents

NameDescription
PowerBoundaryModel
PowerPortModel